Partial discharge characteristics of inverter-fed motor coil samples under ac and surge voltage conditions
Okubo, Hitoshi
13232
Lu, Yonghu
13233
Hayakawa, Naoki
13234
We discussed the partial discharge (PD) characteristics of inverter-fed motor coil samples under surge voltage condition and compared with those under ac voltage application. PD light emission images and PD light intensity waveforms were simultaneously measured to obtain the PD inception characteristics. The differencces in the PD characteristics under ac and surge voltage conditions were investigated for the insuration design of inverter-fed motors. It was found that the PDIV under surge voltage condition was 1.6~1.8 times and 2.3~2.7 times higher than those under ac voltage application for the used and virgin samples respectively, and the PD inception mechanisms were clarified.
journal article
IEEE
2003
application/pdf
2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena
589
592
http://hdl.handle.net/2237/6825
https://nagoya.repo.nii.ac.jp/record/5234/files/EIDP2003_589.pdf
eng
https://doi.org/10.1109/CEIDP.2003.1254923
0-7803-7910-1
Copyright © 2003 IEEE. Reprinted from (relevant publication info). This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of any of Nagoya University’s products or services. Internal or personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution must be obtained from the IEEE by writing to pubs-permissions@ieee.org.