Discharge pattern discrimination in vacuum interrupter with non-contact measurement of shield potential
Kong, Fei
76136
Kojima, Hiroki
76137
Hayakawa, Naoki
76138
Kimura, Toshinori
76139
Tsukima, Mitsuru
76140
Vacuum interrupter
floating electrode
discharge diagnostics
breakdown
surface flashover
Vacuum interrupter has a composite insulation system. When an internal insulation fails, the discharge has complex and various patterns. Previously, based on the discharge development characteristics, we proposed a discrimination method for the discharge pattern in vacuum interrupter. We measured the applied voltage, anode current, and shield potential waveforms, respectively. From the analysis of the measured waveforms, we can estimate the discharge patterns and discharge path lengths. In this paper, a non-contact shield potential measurement was proposed when the shield potential cannot be measured directly. Furthermore, verification tests with this measurement method were conducted and the effectiveness of the discrimination method was confirmed.
journal article
IEEE
2017-11-27
application/pdf
IEEE Transactions on Dielectrics and Electrical Insulation
5
24
3265
3269
1070-9878
https://nagoya.repo.nii.ac.jp/record/25706/files/6512-revised-hayakawa2.pdf
eng
https://doi.org/10.1109/TDEI.2017.006512
“© 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.”