@article{oai:nagoya.repo.nii.ac.jp:00005166, author = {Kurupakorn, C. and Hayakawa, N. and Kashima, N. and Nagaya, S. and Noe, M. and Juengst, K.-P. and Okubo, H.}, issue = {2}, journal = {IEEE Transactions on Applied Superconductivity}, month = {Jun}, note = {We have been developing a High Temperature Superconducting Fault Current Limiting Transformer (HTc-SFCLT) with functions of both superconducting transformer in normal operating condition and superconducting fault current limiter in fault condition. The ratings of the developed HTc-SFCLT are 3-phase, 6.25 kVA, 275/105 V. The secondary coil consists of Melt Cast Processed (MCP)-BSCCO2212/CuNi composite bulk monofilar coils, whereas the primary coil is composed of a copper coil, both of which are immersed in liquid nitrogen bath together with the iron core. Experimental results revealed the operational feasibility of HTc-SFCLT through no-load and short-circuit tests, current limiting test and recovery test. Index Terms.MCP-BSCCO2212, recovery, superconducting.}, pages = {900--903}, title = {Development of high temperature superconducting fault current limiting transformer (HT/sub c/-SFCLT) with Bi2212 bulk coil}, volume = {14}, year = {2004} }