著者 |
Kurimoto, Muneaki
× Kurimoto, Muneaki× Kato, Katsumi× Hanai, Masahiro× Hoshina, Yoshikazu× Takei, Masafumi× Okubo, Hitoshi |
|||||
アクセス権 | ||||||
アクセス権 | open access | |||||
アクセス権URI | http://purl.org/coar/access_right/c_abf2 | |||||
権利 | ||||||
言語 | en | |||||
権利情報 | © 2010 IEEE. Reprinted, with permission, from Kurimoto, Muneaki; Kato, Katsumi; Hanai, Masahiro; Hoshina,Yoshikazu; Takei, Mmasafumi; Okubo, Hitoshi, Application of functionally graded material for reducing electricfield on electrode and spacer interface, Dielectrics and Electrical Insulation, IEEE Transactions on, Feb/2010 | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Functionally graded material (FGM) | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Permittivity | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Electric field | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Spacer | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Epoxy resin | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Filler | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Centrifugal force | |||||
キーワード | ||||||
主題Scheme | Other | |||||
主題 | Gas insulated switchgear (GIS) | |||||
抄録 | ||||||
内容記述タイプ | Abstract | |||||
内容記述 | For the size reduction and the enhancing reliability of electric power equipment, the electric field stress around solid insulators should be considered enough. For the relaxation of the field stress, the application of FGM (Functionally Graded Materials) with spatial distribution of dielectric permittivity (ε-FGM) can be an effective solution. In this paper, we investigated the applicability of ε-FGM for reducing the electric field stress on the electrode surface with contact to the solid dielectrics, which was one of the important factors dominating a long-term reliability of the insulating spacer. Firstly, we carried out numerical simulation of electric field to confirm the reduction of the electric stress by U-shape permittivity distribution. Secondly, we investigated the fabrication feasibility of ε-FGM with the U-shape distribution. Thirdly, we estimated the long-term electrical insulation performance of the ε-FGM. Finally, we verified the applicability and the fabrication technique of the ε-FGM to solid dielectrics for improvement of the electric stress and the long-term insulation performance in electric power equipment. | |||||
言語 | en | |||||
出版者 | ||||||
出版者 | IEEE | |||||
言語 | en | |||||
言語 | ||||||
言語 | eng | |||||
資源タイプ | ||||||
資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
資源タイプ | journal article | |||||
出版タイプ | ||||||
出版タイプ | AM | |||||
出版タイプResource | http://purl.org/coar/version/c_ab4af688f83e57aa | |||||
DOI | ||||||
関連タイプ | isVersionOf | |||||
識別子タイプ | DOI | |||||
関連識別子 | https://doi.org/10.1109/TDEI.2010.5412025 | |||||
ISSN | ||||||
収録物識別子タイプ | PISSN | |||||
収録物識別子 | 1070-9878 | |||||
書誌情報 |
en : Dielectrics and Electrical Insulation, IEEE Transactions on 巻 17, 号 1, p. 256-263, 発行日 2010-02 |
|||||
著者版フラグ | ||||||
値 | author | |||||
URI | ||||||
識別子 | http://hdl.handle.net/2237/14528 | |||||
識別子タイプ | HDL | |||||
URI | ||||||
識別子 | http://dx.doi.org/10.1109/TDEI.2010.5412025 | |||||
識別子タイプ | DOI |